Measurement Contents:
1-50 Harmonic Voltage, Current Distortion, RMS, Phase Angle, Active Power, Reactive Power, Power Factor, Sequence Component, Voltage Flicker, Voltage Fluctuation, Signal Waveform, Spectrum, Voltage Deviation and Frequency.
Measurement Contents:
1-50 Harmonic Voltage, Current Distortion, RMS, Phase Angle, Active Power, Reactive Power, Power Factor, Sequence Component, Voltage Flicker, Voltage Fluctuation, Signal Waveform, Spectrum, Voltage Deviation and Frequency.
SF DZ-4 Ⅲ Power Quality Analyzer
1、Adopt IEC/61000-4-7, IEC61000-4-30 to measure harmonic and inter-harmonics. Minimum resolution of frequency is 5Hz. Sampling period is 10 cycle. It can carry out 0.5 times (25HZ)inter-harmonics group and 0.1 times (5HZ)inter-harmonic calculation.
2、High-speed fault analysis and recording strictly according to transient data exchange mode.
3、5- inch LED full color screen, graphical data display.
4、Provide full support to PQDIF data files.
SF DZ-4II Power Quality Analyzer
1、5-inch full color LCD display, human operation interface.
2、Support keyboard and mouse operation. Support U disk data export.
3、Class Windows human-machine interface, which is humanistic and friendly.
4、Data analysis and report generation
5、More compact structure, more powerful function, more convenient display.
SF DZ-4I Power Quality Analyzer
Combine notebook computer with sampling system of high speed and accuracy to ensure accuracy of sampling signals.
1、Construct powerful power quality analysis system using plentiful software. The system consists of hardware sampling system and analysis software.
2、Adopt a serial port between sampling system and notebook.
Instrument function
1、Signal channel: measure 1×3 phase voltage signal and 1×3 current signal.
2、Measuring content: (power quality indexes made by national standard) 1-50 harmonic voltage, current distortion, valid value, phase angle, active power, inactive power, power factor, sequence component, voltage flicker, voltage fluctuate, signal waveform, spectrum, voltage deviation and frequency.
3、Measuring mode: There are 2 kinds of measuring modes. The first kind is sampling one cycle from signal each time and then do analysis. This method applies to measuring rapid changeable signal source. The second is to carry out 6 times equal interval sampling in 3 seconds. Analyze the measurement result of this 6 times sampling using FFS and then carry out RMS processing to distinguish transient phenomenon and harmonic.
Background Software Function
1、Power Quality Real-time Display: Real-time monitor、record at regular time、print out various power quality indexes.
2、Data Analysis: draw variation curve、harmonic distribution graph、statistical analysis、qualification rate calculation.
3、Power Quality Report Form: generate power quality report form at any time.
Measuring Connection
1、The front panel has voltage measurement socket “U”If measure phase voltage(Y-connection), please use plug marked “Y”If measure line voltage(△-connection), please use plug marked “△”
2、When measuring current signal, please plug clamp meter into the socket of the front Panel, and then carry out measuring.
Technical Indexes
Voltage measuring range
AC voltage 10 - 400V
Current measuring range
AC current 0.05 - 6A
Frequency measuring range
47.5~52.5Hz
Harmonic analysis range
00 – 50 times harmonic,
“00”indicates voltage total distortion and total harmonic current valid value
Harmonic voltage ratio
Uh≥1%UN σ≤±5%Uh
Uh<1%UN σ≤±0.05%UN
Harmonic current ratio
Ih<±3%IN σ≤±0.15%IN
Accuracy of basic indexes
Voltage derivation error≤±0.5%;
voltage fluctuation error≤±5%;
flicker error≤±5;voltage dissymmetry factor absolute error< 0.2;
current dissymmetry factor absolute error< 1%;
frequency measurement error< 0.01Hz
Voltage side input DC
> 100KΩ
Current side input DC resistance
< 0.1Ω
resistance
Working power supply
Voltage: AC220V±20% Frequency: 45-55Hz
Voltage measuring range
AC voltage 10 - 400V
Current measuring range
AC current 0.05 - 6A
Frequency measuring range
47.5~52.5Hz
Harmonic analysis range
00 – 50 times harmonic,
“00”indicates voltage total distortion and total harmonic current valid value
Harmonic voltage ratio
Uh≥1%UN σ≤±5%Uh
Uh<1%UN σ≤±0.05%UN
Harmonic current ratio
Ih≥±3%IN σ≤±5%Ih
Ih<±3%IN σ≤±0.15%IN
Accuracy of basic indexes
Voltage derivation error≤±0.5%;
voltage fluctuation error≤±5%;
flicker error≤±5;voltage dissymmetry factor absolute error< 0.2%;
current dissymmetry factor absolute error< 1%;
frequency measurement error< 0.01Hz
Voltage side input DC
> 100KΩ
Current side input DC resistance
< 0.1Ω
resistance
Working power supply
Voltage:AC220V±20% Frequency:45-55Hz
Executive Standard
Standard No.
Standard name
Note
GB/T 15945—2008
Power quality power system frequency deviation
GB/T 12325—2008
Power quality supply voltage deviation
GB/T 15543—2008
Power quality 3-phase voltage unbalance factor
GB/T 12326—2008
Power quality voltage fluctuation and flicker
GB/T 14549—1993
Power quality utility grid harmonic
GB/T 19862—2005
Power quality monitoring equipment general requirement
For more information, please contact EECTECH