Make Your Industrial Purchase Cheaper, Faster, Easier, and Better
伊伊西科技(北京)有限公司
EEC TECHNOLOGY (BEIJING) CORP., LTD

  Hot Line

  +86 134 6671 4221​

P
Hot Search: CK-625, CCGS, CWM-75L, TV1547, 9T94A, ITL12-1, FN1000, GM2200, DA7250, IM9500 ...
P​​
                     
               
CURRENT LOCATION:​​​
 产品中心​TECH 
Outdoor type special regulator

Outdoor type special regulator

The outdoor cabinet can be used according to the protection level for various harsh environmental conditions. The IP55 and IP56 chassis are basically isolated from the external environment and have a heat exchange cooling system. The anti-corrosion level meets the 1000-hour standard hot and humid salt spray test requirements.

0.00
0.00
  
商品描述

The outdoor cabinet can be used according to the protection level for various harsh environmental conditions. The IP55 and IP56 chassis are basically isolated from the external environment and have a heat exchange cooling system. The anti-corrosion level meets the 1000-hour standard hot and humid salt spray test requirements.




Outdoor type special regulator technical parameters

Outdoor special regulator basic indicators

Protective function

Input voltage

380V ± 20% or wide voltage special definition

Overpressure

Output exceeds rated voltage by 10% (adjustable), delay 3-5 seconds to cut off output power

Output voltage

380V±5% selectable

Undervoltage

Output exceeds rated voltage -15% (adjustable), delay 3-5 seconds to cut off output power

Voltage regulation accuracy

1-5% can be set

Delay

2 seconds to cut off the output power

Frequency

50Hz/60Hz

Short circuit

Cut off the output power when the load device is shorted

Strain time

≤0.05s

Overcurrent

When the rated output current is exceeded, the output power is cut off after 3-5 seconds delay.

Stable schedule

When the input voltage changes by 10% relative to the rated value, the stability time is 1s.

Reverse phase

When an error occurs in the three-phase electrical phase sequence, the machine alarms and cuts off the output power.

 

Missing phase

Bypass

Power supply manual or automatic DC device when the regulator is faulty or repaired

Other indicators

Attachment waveform distortion

≤1%

Withstand voltage

The whole machine has no breakdown and no arcing at 2500VAC/min.

Noise

55dB

Insulation resistance

Machine to ground5MΩ

Efficiency

More than 95% below 50KVA, more than 98% above 100KVA

EM filter device

Can effectively filter harmonic interference of the power grid (optional configuration)

Relative humidity

20%-95%

Lightning protection device

When the power grid changes instantaneously and inductive lightning strikes, it can protect against inrush current

Way of working

Can be unattended for a long time.

Monitoring interface

With R232, RS485 interface, remote control, remote signaling, telemetry (optional configuration)


Note: SBW-HW series outdoor regulators are non-standard customized products. EECTECH can customize outdoor products that meet user requirements according to customers' actual use conditions.


For more information, please contact EECTECH









1. Outdoor type special regulator has large capacity, high efficiency, no waveform distortion, stable voltage regulation, wide load, and outdoor load regulator. It can withstand transient overload and can be continuous for a long time. Based on many advantages such as work, manual/automatic random switching, outdoor cabinets can be used according to various protection levels under different environmental conditions. The IP55 and IP56 chassis are basically isolated from the external environment and have a heat exchange cooling system. The 1000-hour standard wet heat salt spray test requires that the outdoor special-purpose voltage regulator is especially suitable for use under the salt spray environment of the island.

2. Outdoor type special voltage regulator can be widely used in industrial, agricultural, transportation, post and telecommunications, military, railway, scientific research and other fields of large-scale electromechanical equipment, metal processing equipment, production lines, construction engineering equipment, elevators, medical equipment, embroidery Light textile equipment, air conditioners, radio and television, household appliances, lighting, etc. need to be regulated and installed in outdoor or other harsh environments.

3. SBW-HW series outdoor special regulator can be used outdoors or in other harsh environments. The normal conditions of use are:

     1), ambient temperature: -15 ° C - +50 ° C
     2), altitude: <1000M
     3) Relative humidity: 20%-95%
     4), IP55, IP56 chassis can be applied to dust, dirt and island salt spray corrosive media.
     5) There is no serious vibration or bumps in the installation site.







Send Inquiry​​