Overview of APF Active Power Filter Products
Active Power Filter (APF) is connected to the power grid in parallel. Through real-time detection of the harmonic and reactive components of the load, and using PWM transformation technology, the harmonic and reactive components are injected into the power supply and distribution system with the same magnitude and opposite direction of the current. It can suppress harmonics and compensate reactive power dynamically.
Performance Characteristics of APF Active Power Filter
1. It can compensate 2-50 harmonics or select specific harmonics to compensate separately.
2. Flexible compensation methods: only compensating harmonics; harmonics and reactive power compensation; only compensating reactive pow
3. It has remote communication interface and can be monitored by PC in real time. Intelligent control circuit, high reliability.
4. Advanced power conversion technology, flexible compensation mode and simple operation.
5. The equipment has high reliability and can withstand high temperature, high charged dust and heavy corrosion environment.
APF Active Power Filter Technical Indicators
Index
Parameters
Rated voltage
AC380V±20%,AC480V±20%,AC600V±20%
Working frequency range
50Hz(60Hz)±10%
Communication mode
RS485 Interface, Modbus Communication Protocol
Protection Level
IP21 or user customization
Cooling mode
Air cooling
Installation mode
Full cabinet mode
Ambient temperature
-10~40℃
Relative humidity
Maximum 95%, no condensation
Installation altitude
≤1000m,Special customization over 1000m
Connection mode
Three-phase three-wire, up-line or down-line optional
Filtering range
2-51 harmonics (each harmonic can be set separately)
Filtering effect
Current distortion rate≤5%
Reactive Power Compensation Effect
Choose whether reactive power compensation or not
Active power loss
≤2.5%
Response time
<10ms
Parallel number of stations
Unlimited